Augšējā kopņu sistēma līdz 3200 A (EN)
xEnergy product features Busbar location at top up to 3200 A
- Clear separation into functional units (Form 1 to Form 4)
- Enclosures for combination and separate mounting
- Degree of protection IP 31 or IP 55
- Height 2000 mm
- Widths 425 mm, 600 mm, 800 mm, 1000 mm, 1200 mm
- Main busbar location at top, up to 1600 A at 400 mm section depth
- Main busbar location at top, up to 3200 A at 600 mm section depth
- All mounted units as TTA’s
- Network systems TN-C, TN-C-S, TN-S, TT, IT
- Colour RAL 7035 (others on demand)
XP power sections
- Feeders, outgoers with NZM 4 circuit-breakers up to 1600 A or IZM up to 3200 A
- Fixed mounted and withdrawable units
- 3- or 4-pole circuit-breakers
- Cable or busbar trunking connection from bottom
|
|
XF fixed mounted sections
- Outgoers with PKZ and NZM circuit-breakers up to 630 A
- Feeders or outgoers with NZM 4 circuit-breakers and IZM up to 1600 A
- Fixed mounted and withdrawable units
- 3- or 4-pole circuit-breakers
- Cable connection from below or rear
|
|
XG freely configurable sections
- Mounting systems for rail-mounted service installation devices for conventional service distribution boards
- Individual fixed mounted units on mounting plates up to 630 A, such as soft starters, frequency inverters, PFC modules
- Automation and control applications
- Adapter systems for motor starters (xStart)
|
 |
|
 |
|
 |
|